Rockwell Automation Publication 280E-UM001B-EN-P – July 2012 143
Bulletin 280E/281E/284E Programmable Parameters Chapter 7
Produced Assembly Config Group
Base Trip
The parameter provides the Base
Module Trip Status.
Parameter Number 63
Access Rule GET
Data Type WORD
Group Basic Status
Units
Minimum Value 0
Maximum Value 65535
Default Value 0
Bit
Warning
1514131211109876543210
——————————————— X
EEPROM Fault
—————————————— X
Internal Comm
————————————— X —— Hardware Fault
———————————— X ——— Control Module
XXXXXXXXXXXX————
Reserved
Int00DeviceOut Cfg
This parameter is used to specify
Int00DeviceOut of produced assembly
150 or 151.
Parameter Number 13
Access Rule GET/SET
Data Type USINT
Group Produced Assembly Config
Units
Minimum Value 0
Maximum Value 263
Default Value 1
Int01DeviceOut Cfg
This parameter is used to specify
Int01DeviceOut of produced assembly
150 or 151.
Parameter Number 14
Access Rule GET/SET
Data Type USINT
Group Produced Assembly Config
Units
Minimum Value 0
Maximum Value 263
Default Value 4