Rockwell-automation 284E ArmorStart with EtherNet/IP - User Manual Manual de usuario Pagina 285

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 348
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 284
Rockwell Automation Publication 280E-UM001B-EN-P – July 2012 285
CIP Information Appendix B
Connection Manager Object
CLASS CODE 0x0006
The following class attributes will be supported for the Connection Manager
Object.
Two Class 1 connections for I/O transfer will be supported.
Six Class 3 explicit connections will be supported.
The following instance attributes will be supported:
Instance 166 Consumed Inverter Type Starter with Network Inputs
ByteBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
0 Out B Out A JogReverse JogForward ResetFault RunReverse RunForward
1 DriveInput4 DriveInput3 DriveInput2 DriveInput1 DecelCtrl_1 DecelCtrl_0 AccelCtrl_1 AccelCtrl_0
2 FreqCommand (Low) (xxx.x Hz)
3 FreqCommand (High) (xxx.x Hz)
4 Pt07DeviceIn Pt06DeviceIn Pt05DeviceIn Pt04DeviceIn Pt03DeviceIn Pt02DeviceIn Pt01DeviceIn Pt00DeviceIn
5 Pt15DeviceIn Pt14DeviceIn Pt13DeviceIn Pt12DeviceIn Pt11DeviceIn Pt10DeviceIn Pt9DeviceIn Pt8DeviceIn
Attribute ID Access Rule Name Data Type Value
1 Get Revision UINT 1
2 Get Max Instance UINT
3 Get Number of Instances UINT
4 Get Optional Attribute List Array of UINT
6 Get Max Number Class Attribs UINT
Attribute ID Access Rule Name Data Type Value
1 Get/Set Open Requests UINT Number of Forward Open service requests received.
2 Get/Set Open Format Rejects UINT
Number of Forward Open service requests which were
rejected due to bad format.
3 Get/Set Open Resource Rejects UINT
Number of Forward Open service requests which were
rejected due to lack of resources.
4 Get/Set Open Other Rejects UINT
Number of Forward Open service requests which were
rejected for reasons other than bad format or lack of
resources.
5 Get/Set Close Requests UINT Number of Forward Close service requests received.
6 Get/Set Close Format Requests UINT
Number of Forward Close service requests which were
rejected due to bad format.
7 Get/Set Close Other Requests UINT
Number of Forward Close service requests which were
rejected for reasons other than bad format.
8 Get/Set Connection Timeouts UINT
Total number of connection timeouts that have occurred in
connections controlled by this Connection Manager
Vista de pagina 284