Chapter 5 –Programming
5-35
Faults
This group of parameters provides information and programmed settings on commonly viewed drive faults.
[
F
a
u
l
t
B
uff
er
0
-
3]
Parameter # 86-89 Factory Default None
[
F
a
u
l
t
B
uff
er
0
-
3]
Parameter Type Read Only
These parameters store the last (4) faults that occur. If the
same fault occurs multiple times in a row, it will only be
stored once. [Fault Buffer 0] through [Fault Buffer 3] can
only be cleared by ‘‘Reset Defaults” from EEPROM mode
or [Set Defaults] parameter. This will leave a ‘‘F48” in
[Fault Buffer 0].
Units None Buffer
0
1
2
3
Last Fault, stored in EEPROM
Fault from Buffer 0, Stored in EEPROM
Fault from Buffer 1, Stored in EEPROM
Fault from Buffer 2, Stored in EEPROM
[
C
lear
F
a
u
l
t]
Parameter # 51 Factory Default ‘‘Ready”
[
C
lear
F
a
u
l
t]
Parameter Type Read & Write
This parameter is used to clear a fault and return the drive
to ready status if the fault condition no longer exists.
IMPO TA T: C e r u ] s p ru g drve s
Units None Displays ‘‘Ready”
Display after function complete
IMPO
R
TA
N
T:
[
C
l
e
a
r
Fa
u
lt
]
will
s
to
p
a
ru
nnin
g
dr
i
ve
. Al
s
o
[Clear Fault] does not clear [Fault Buffer 0] through
[Fault Buffer 3].
‘‘Clear Fault”
Attempts to clear fault
[
Cu
r
L
im
Tr
i
p
En
]
Parameter # 82 Factory Default ‘‘Default Run”
[
Cu
r
L
im
Tr
i
p
En
]
Parameter Type Read & Write
This setting determines whether or not exceeding the
se g [ rren L use D g s Curre
Units None Setting ‘‘Trip @ I Lim”
A Diagnostic Current Limit Fault is generated
se
ttin
g
in
[
Cu
rren
t
L
imit] will ca
use
a
D
ia
g
no
s
tic
Curre
nt
Limit Fault (Fault F36).
‘‘Default Run”
No fault generated
[L
i
ne
Lo
ss F
a
u
l
t]
Parameter # 40 Factory Default ‘‘F03 Enable”
[L
i
ne
Lo
ss F
a
u
l
t]
Parameter Type Read & Write
This setting determines whether a 15% drop in DC Bus
v ge h ve e e per r use ‘‘ er
Units None Setting ‘‘UVolt Run”
‘‘Power Loss Fault” Disabled
v
olta
ge
will
h
a
ve
no
e
ff
e
ct on o
per
ation o
r
ca
use
a
‘‘
Pow
er
Loss Fault” (fault F03).
‘‘FO3 Enable”
Drive Trips at 85% of nominal bus voltage.