Chapter 5 –Programming
5-28
[S
ki
p
F
re
q
Band
]
Parameter # 35 Factory Default 0 Hz
[S
ki
p
F
re
q
Band
]
Parameter Type Read & Write Minimum 0 Hz
This parameter determines the band width around a [Skip
Frequency]. The actual band width is 2 [Skip Freq
Band] – 1/2 the band above and 1/2 the band below the
[Skip Frequency] setting. “0” Disables All Skip
Frequencies.
Units 1 Hz Maximum 15 Hz
'
Figure 5.15 Skip Frequency Band
b
y
Two times
[Skip Freq Band]
Setting
'
Command Frequency
Skip Frequency
Frequency
Time
Drive Output
Frequency
Setting
a
[MOP Increment]
Parameter # 22 Factory Default 0.00 Hz/Sec
[MOP
In
c
re
m
en
t]
Parameter Type Read & Write Minimum 0.00
This parameter sets the rate of increase or decrease to
the [MOP Hertz] command frequency. IMPORTANT:
The MOP function can only be invoked through a serial
communications module.
Units 1 Hz/Sec Maximum 255 Hz/Sec