Appendix B –
Serial Communications
B-7
Table B.4 Parameter Grouping/User Settings (cont.)
Group Parameter Name Param-
eter #
Display
Units
Drive Units
Scale Factor ➁
Min Max Factory Setting User‘s
Setting
Minimum Freq 16 Hz 1 0 120 0
Maximum Freq 19 Hz 1 40 400 60
Base Frequency 17 Hz 1 40 400 60
Base Voltage 18 Volts 1 25% of
DRV
Maximum Drive Rated Volts Maximum DRV
Break Frequency 49 Hz 1 0 120 0
Break Voltage 50 Volts 1 0 50% of Max Drive Rated Volts 0
et Up
Maximum Voltage 20 Volts 1 25% of
DRV
Maximum Drive Rated Volts Maximum DRV
d
DC Boost Select 9 Text ➀ 1 –– –– No Boost
nce
Start Boost 48 Volts 1 0 25% of Max. Drive Rated Volts 0
va
Run Boost 83 Volts 1 0 25% of Max. Drive Rated Volt 0
Adv
PWM Frequency 45 kHz 10 2.0 8.0 4.0
Analog Invert 84 Text ➀ 1 –– –– Disabled
4–20 mA Loss Sel 81 Text ➀ 1 –– –– Stop/Fault
Stop Select 10 Text ➀ 1 –– –– Ramp
DC Hold Time 12 Seconds 1 0 15 0
DC HoId Level 13 Volts 1 0 25% of Max. Drive Rated Volt 0
DB Enable 11 Text ➀ 1 –– –– Disabled
Motor Type 41 Text ➀ 1 –– –– Induc/Reluc
Compensation 52 Text ➀ 1 –– –– No Comp
➀ Refer to Table B.5 on pages B-13, B-14 and B-15 for the numerical equivalent of the text descriptions. ➁ Refer to page B-2.