Appendix B –
Serial Communications
B-6
Table B.4 Parameter Grouping/User Settings (cont.)
Group Parameter Name Param-
eter #
Display
Units
Drive Units
Scale Factor
Min Max Factory Setting User‘s
Setting
Input Mode 21 Text 1 –– –– Three Wire
Freq Select 1 5 Text 1 –– –– Adapter 1
p
Accel Time 1 7 Seconds 10 0.0 3600.0 10.0
e
t U
p
Decel Time 1 8 Seconds 10 0.0 3600.0 10.0
Set
Base Frequency 17 Hz 1 40 400 60
S
Base Voltage 18 Volts 1
25% of DRV
Drive Rated Volts Drive Rated Volts
Maximum Voltage 20 Volts 1
25% of DRV
Drive Rated Volts Drive Rated Volts
Minimum Freq 16 Hz 1 0 120 0
Maximum Freq 19 Hz 1 40 400 60
Stop Select 10 Text 1 –– –– Ramp
Current Limit 36 % 1 20% of
DRC
150% of Drive Rated Current (DRC) 150% of DRC
Overload Mode 37 Text 1 –– –– No Derating
Overload Current 38 Amps 100 = DRC 20% of
DRC
115% of Drive Rated Current (DRC) 115% of DRC
Sec Curr Limit 141 % 1 0 150% of Drive Rated Current (DRC) 0
Refer to Table B.5 on pages B-13, B-14 and B-15 for the numerical equivalent of the text descriptions. Refer to page B-2.