Chapter 6 –Troubleshooting and Fault Information
6-5
Table 6.B Bulletin 1305 Fault Descriptions (cont.)
Fault Name & Number Fault Description Action to Take
Motor Mode FIt
2
Internal error. Reset drive to factory defaults.
Mo
t
or
Mode
F
I
t
F24
Int
er
nal
err
o
r
. R
ese
t
dr
i
ve
to facto
ry
de
fa
u
lt
s
.
Motor Stall Fault
F6
The motor is stalled. If the motor is drawing excessive current, the motor load is
excessive and will not allow the drive to accelerate to set speed.
A longer accel time or a reduced load may be required.
Neg Slope Fault
F35
Drive software detected a portion of the volts/Hz curve with a
negative slope.
Check drive programming.
1. [Maximum Voltage] parameter must be greater than or
equal to [Base Voltage].
2. [Base Voltage] parameter must be greater than 1.5 X [Start
Boost].
3. If the [DC Boost Select] parameter is set to ‘‘Break Point,’’
[Base Voltage] must be greater than [Break Voltage] and
[Break Voltage] must be greater than [Start Boost].
4. [Maximum Freq] must be greater than or equal to [Base
Frequency]
Network Error Network Error 0 – Error 6 ScanPort Error
Network Error 7 – Error 9 Communications Error
1. Press the “Up” or “Down” arrow to clear the message from
the HIM display.
2. Unplug the HIM from the cable or drive and re-connect.
3. Check for external noise sources.