Appendix A
Block Diagram and Specifications
A-5
Table A.1 Specifications (cont.)
Motor Protection Electronic Overload Protection. Adjustable from 20% to 115% (Motor FLA)
Overload Pattern #0 Flat response over speed range (no current derating)
Overload Pattern #1 Current derating below 25% of Base Speed
Overload Pattern #2 Current derating below 50% of Base Speed
Accel/Decel Time(s) 0.1 to 3600 Seconds, independently set (2 Accel, 2 Decel)
Preset Speeds 0 to 400 Hz, 7 selections, independently set
Jog Input 0 to 400 Hz
Stopping Modes 4 modes programmable
Ramp to stop 0.1 to 3600 seconds
Coast Stops all PWM Output
DC Brake to stop Applies DC Voltage to the Motor for 0 to 15 seconds
S-Curve Ramps to stop with S-Curve profile
PROTECTIVE FEATURES
Excessive Temperature Embedded temperature sensor trips if factory preset level is exceeded
Over/Under Voltage DC Bus voltage is monitored for safe operation
Power Ride Through Minimum ride through 15mS under nominal conditions
Control Ride Through Minimum ride through is 0.5 Seconds – typical value 2 seconds
Ground Short Any output short to ground, detected prior to start
Line Voltage Transients Inherent MOV (varistor) protection
Output Short Circuit Inherent short circuit protection provided within IPM
See Page 5-12 for NEC and UL information. Conditions such as ambient temperature, overload, duty cycle, etc. can affect tripping
time.