Chapter 5 –Programming
5-14
This group contains parameters that are required to setup advanced functions of the drive such as custom
Volts per Hertz settings and dynamic braking.
Advanced Setup
[M
i
n
imum F
re
q]
Parameter # 16 Factory Default 0 Hz
[M
i
n
imum F
re
q]
Parameter Type Read & Write Minimum 0 Hz
This parameter sets the lowest frequency the drive will
output. IMPORTANT: All analog inputs to the drive
(4-20mA, 0-10V, Remote Pot) are scaled for the range
[Minimum Freq] to [Maximum Freq].
Units 1 Hz Maximum 120 Hz
IMPORTANT: This parameter can not be pro-
grammed while the drive is running.
[Max
imum F
re
q]
Parameter # 19 Factory Default 60 Hz
[Max
imum F
re
q]
Parameter Type Read & Write Minimum 40 Hz
This parameter sets the highest frequency the drive will
output. IMPORTANT: All analog inputs to the drive
(4-20mA, 0-10V, Remote Pot) are scaled for the range
[Minimum Freq] to [Maximum Freq]
Units 1 Hz Maximum 400 Hz
IMPORTANT: This parameter can not be pro-
grammed while the drive is running.
[Ba
s
e
F
re
qu
en
c
y
]
Parameter # 17 Factory Default 60 Hz
[Ba
s
e
F
re
qu
en
c
y
]
Parameter Type Read & Write Minimum 40 Hz
This value should be set to the motor nameplate Rated
Frequency.
Units 1 Hz Maximum 400 Hz