Chapter 1 –Information and Precautions
1-6
Table 1.A Drive Rating and Derating Guidelines
Motor Rating
Voltage
Catalog
3 O Input 1 O Input
Rating
Numb
IP30
HP kW
Output ➀➁
Current (A)
HP kW
Output ➀➁
Current (A)
1305-AA02A 1/2 0.37 2.3 – – –
200-230V
1305-AA03A 3/4 0.55 3 1/2 0.37 2.3
50/60 Hz
1305-AA04A
1 0.75 4.5 3/4 0.55 3
1305-AA08A 2 1.5 8 1 0.75 4.5
1305-AA12A 3 2.2 12 ➂ 2 1.5 8 ➂
1305-BA01A 1/2 0.37 1.3
380-460V
1305-BA02A 3/4 0.55 1.6
50/60 Hz
1305-BA03A
1 0.75 2.3
1305-BA04A 2 1.5 4
ot A
ailabl
1305-BA06A 3 2.2 6 ➃
1305-BA09A 5 4.0 9 ➄
In general:
When operating the drive in an ambient temperature at or near
the maximum operating temperature (50°C), the following
derating guidelines are recommended to guard against
overheating depending on application and operating conditions.
➀ Motor Full Load Amps (FLA) should not exceed the drive output current rating.
➁ If the [PWM Frequency] is set above 4kHz, the output current must be derated per the
chart on page 5-20.
➂ Output current value listed for 200V input voltage. At 230V input voltage, output
current is 9.6A for 3 phase and 6.8A for single phase.
➃ Output current value listed for 380V input voltage. At 415V input voltage, output
current is 5.3A. At 460V input voltage, output current is 4.8A.
➄ Output current value listed for 380V input voltage. At 415V input voltage, output
current is 8.4A. At 460V input voltage, output current is 7.6A.