Chapter 5 –Programming
5-10
Set Up Group (cont.)
imum V
t
g
]
Parameter # 20 Factory Default Max. Drive Rated Volts
imum V
t
g
]
Parameter Type Read & Write Minimum 25% of Max. Drive Rated Voltage
This parameter sets the highest voltage the drive will
output. IMPORTANT: [Maximum Voltage] must be greater
than or equal to [Base Voltage].
Units 1 Volt Maximum 100% of Max. Drive Rated Volts
i
imum F
q]
Parameter # 16 Factory Default 0 Hz
i
imum F
q]
Parameter Type Read & Write Minimum 0 Hz
This parameter sets the lowest frequency the drive will
output. IMPORTANT: All analog inputs to the drive
(4-20mA, 0-10V, Remote Pot) are scaled for the range
[Minimum Freq] to [Maximum Freq].
Units 1 Hz Maximum 120 Hz
IMPORTANT: This parameter can not be pro-
grammed while the drive is running.
imum F
q]
Parameter # 19 Factory Default 60 Hz
imum F
q]
Parameter Type Read & Write Minimum 40 Hz
This parameter sets the highest frequency the drive will
output. IMPORTANT: All analog inputs to the drive
(4-20mA, 0-10V, Remote Pot) are scaled for the range
[Minimum Freq] to [Maximum Freq].
Units 1 Hz Maximum 400 Hz
IMPORTANT: This parameter can not be pro-
grammed while the drive is running.