
Chapter 5 –Programming
5-25
Frequency Set Group (cont.)
D
c
im
]
Parameter # 31 Factory Default 10.0 Sec
D
c
im
]
Parameter Type Read & Write Minimum 0.0 Sec
This value determines the time it will take the drive to ramp
from [Maximum Freq] to 0 Hz. The rate is linear unless
[S Curve] is ‘‘Enabled” or [Stop Select] is set to
‘‘S-Curve.” It applies to any decrease in command
frequency unless [Decel Time 1] is selected. Refer to
charts on Pages 5-26 and 5-27.
Units 0.1 Second Maximum 3600.0 Sec
s
t F
q 1
]
Parameter # 27-29 & 73-76 Factory Default 0.0 Hz
s
t F
q 1
]
Parameter Type Read & Write Minimum 0.0 Hz
These values set the frequencies that the drive will output
when selected. Refer to charts on Pages 5-26 and 5-27.
Units 0.1 Hz Maximum 400.0 Hz
ki
F
q 1
3]
Parameter # 32-34 Factory Default 400 Hz
ki
F
q 1
3]
Parameter Type Read & Write Minimum 0 Hz
These values, in conjunction with [Skip Freq Band],
create a range of frequencies at which the drive will not
operate continuously.
Units 1 Hz Maximum 400 Hz
Programming the drive for Frequency Source and Accel/Decel Control
Use NO TAG and NO TAG to determine which frequency source and Accel/Decel Time are suitable to your application. Switch or
contact inputs at terminal TB2 are used to select functionality based on how you program parameters (26) and (72).
Comentarios a estos manuales