156 Rockwell Automation Publication 750-PM001J-EN-P - October 2014
Chapter 3 Drive Port 0 Parameters
DIAGNOSTICS
Status
935 Drive Status 1
Drive Status 1
RO 32-bit
Integer
Present operating condition of the drive.
Bit 0 “Ready” – When parameter 150 [Digital In Cfg] option 1 “Run Level” is selected and the run command is low, this bit will also be low.
File
Group
No. Display Name
Full Name
Description
Values
Read-Write
Data Type
Options
Regen
Motor OL
Enable On
Bus Frq Reg
Cur Limit
At Limit
At Home
AtZero Speed
Torque Mode
PositionMode
Speed Mode
DB Active
DC Braking
Stopping
Jogging
Running
Reserved
SpdRef Bit 4
SpdRef Bit 3
SpdRef Bit 2
SpdRef Bit 1
SpdRef Bit 0
Manual
At Speed
Faulted
Alarm
Decelerating
Accelerating
Actual Dir
Command Dir
Active
Ready
Default00000000000000000000000000000000
Bit 313029282726252423222120191817161514131211109 8 7 6 5 4 3 2 1 0
0 = Condition False
1 = Condition True
Table 935A: Reference Status
Bit1413121110Reference Source Parameter
00001Auto, Ref A 545
00010Auto, Ref B 550
00011Auto, Preset 3 573
00100Auto, Preset 4 574
00101Auto, Preset 5 575
00110Auto, Preset 6 576
00111Auto, Preset 7 577
10000MAN, Port 0, DIGIN SEL 563
10001MAN, Port 1 871
10010MAN, Port 2 872
10011MAN, Port 3 873
10100MAN, Port 4 874
10101MAN, Port 5 875
10110MAN, Port 6 876
11101MAN, Port 13 INT. ENET 877
11110MAN, Port 14 DRV LOGIX878
11111ALT MAN REF SEL 328