346 Rockwell Automation Publication 750-PM001J-EN-P - October 2014
Chapter 6 Troubleshooting
13041 PCCC IO Timeout The adapter has not received a PCCC Control message for longer than the PCCC
Control Timeout.
13042 Msg Ctrl Open The timeout attribute in either the CIP Register or Assembly object was written
with a non-zero value, allowing control messages to be sent to the adapter.
13043 Msg Ctrl Close The timeout attribute in either the CIP Register or Assembly object was written
with a zero value, disallowing control messages to be sent to the adapter.
13044 Msg Ctrl Timeout The timeout attribute in either the CIP Register or Assembly object elapsed
between accesses of those objects.
13045 Peer IO Open The adapter received the first Peer I/O message.
13046 Peer IO Timeout The adapter has not received a Peer I/O message for longer than the Peer I/O
Timeout.
13047…
13054
Reserved
13055 BOOTP Response The adapter received a response to its BOOTP request.
13056 E-mail Failed The adapter encountered an error attempting to send a requested e-mail
message.
13057 Option Card Flt The adapter experienced a generic fault condition (drive only).
13058 Module Defaulted The adapter has been set to defaults.
13059 Net Memory Mgmt The adapter encountered an error with buffer counters or lists.
Code Event Description