54 Rockwell Automation Publication 750-PM001J-EN-P - October 2014
Chapter 3 Drive Port 0 Parameters
Drive (Port 0) Motor Control
File
File
Group
No. Display Name
Full Name
Description
Values
Read-Write
Data Type
MOTOR CONTROL
Motor Data
25 Motor NP Volts
Motor Nameplate Volts
Rated volts shown on the motor nameplate.
Units:
Default:
Min/Max:
V AC
Based on Drive Rating and Voltage Class
0.10 / Based on Drive Rating and Voltage Class
RW Real
26 Motor NP Amps
Motor Nameplate Amps
Rated full load amps shown on the motor nameplate.
Units:
Default:
Min/Max:
Amps
Based on Drive Rating
0.01 / 14200.00
RW Real
27 Motor NP Hertz
Motor Nameplate Hertz
Rated frequency shown on the motor nameplate.
Units:
Default:
Min/Max:
Hz
Based on Drive Rating
2.00 / 650.00
RW Real
28 Motor NP RPM
Motor Nameplate Revolutions Per Minute
Rated RPM shown on the motor nameplate.
Units:
Default:
Min/Max:
RPM
Based on Drive Rating
1.0 / 40000.0
RW Real
29 Mtr NP Pwr Units
Motor Nameplate Power Units
Power units shown on the motor nameplate.
Default:
Options:
Based on Drive Rating
0 – HP
1 – kW
RW 32-bit
Integer
30 Motor NP Power
Motor Nameplate Power
Rated power shown on the motor nameplate.
Units:
Default:
Min/Max:
HP (P29 = 0)
kW (P29 = 1)
Based on Drive Rating
0.00 / 2000.00
RW Real
31 Motor Poles
Motor Poles
Number of poles in the motor.
Units:
Default:
Min/Max:
Pole
4
2 / 200
RW 32-bit
Integer