222 Rockwell Automation Publication 750-PM001J-EN-P - October 2014
Chapter 4 Port 10 and Port 11 Parameters
File
Group
No. Display Name
Full Name
Description
Values
Read-Write
Data Type
CONVERTER COMMON
Configuration
16 Gnd Cur Flt Lvl
Ground Current Fault Level
The converter system peak ground current fault threshold. The converter will fault if the
peak input ground current exceeds this threshold for five line cycles on any converter.
Units:
Default:
Min/Max:
Amps
600.0
0.0 / 3000.0
RW Real
File
Group
No. Display Name
Full Name
Description
Values
Read-Write
Data Type
CONVERTER COMMON
Metering
20 L1 Phase Curr
Line 1 Phase Current
The converter system AC line 1 (R) RMS input current. This is the sum of all line 1 (R)
phase currents from all online converters.
Units:
Default:
Min/Max:
Amps
0.0
0.0 / 15000.0
RO Real
21 L2 Phase Curr
Line 2 Phase Current
The converter system AC line 2 (S) RMS input current. This is the sum of all line 2 (S)
phase currents from all online converters.
Units:
Default:
Min/Max:
Amps
0.0
0.0 / 15000.0
RO Real
22 L3 Phase Curr
Line 3 Phase Current
The converter system AC line 3 (T) RMS input current. This is the sum of all line 3 (T)
phase currents from all online converters.
Units:
Default:
Min/Max:
Amps
0.0
0.0 / 15000.0
RO Real
23 Heatsink Temp
Heatsink Temperature
The converter system heatsink temperature. This is the maximum heatsink temperature
from all online converters.
Units:
Default:
Min/Max:
DegC
0.0
–/+200.0
RO Real
24 SCR Temp
SCR Temperature
The converter system SCR temperature. This is the maximum SCR temperature from all
online converters.
Units:
Default:
Min/Max:
DegC
0.0
–/+200.0
RO Real
25 Gate Board Temp
Gate Board Temperature
The converter system gate board temperature. This is the maximum gate board
temperature from all online converters
Units:
Default:
Min/Max:
DegC
0.0
–/+200.0
RO Real
File
Group
No. Display Name
Full Name
Description
Values
Read-Write
Data Type
CONVERTER COMMON
Testpoints
30
32
Testpoint Sel 1
Testpoint Sel 2
Testpoint Selection 1, 2
Selects a source for [Testpoint Val n]. Used by the factory, typically for diagnostic
purposes.
Default:
Min/Max:
0
0 / 65535
RW 32-bit
Integer
31
33
Testpoint Val 1
Testpoint Val 2
Testpoint Value 1, 2
Displays data selected by [Testpoint Sel n].
Default:
Min/Max:
0.000000
–/+220000000.000000
RO Real
Comentarios a estos manuales