Appendix B Application Notes
3. Configure the message instructions.
a. Click the Configuration tab. See Figure 81
.
Figure 81 - Message Configuration Screen - Configuration Tab
b. In the Message Type field, click the down arrow to select CIP Generic.
c. In the Service Type field, click the down arrow to select Get Attribute
Single.
d. In the Class field, enter 93 (hex); use the EtherNet/IP DPI Parameter
Object.
e. Set the Instance to 482. This field defines the parameter that you want
to obtain.
f. Set the Attribute to 9. This field defines that you want to retrieve the
parameter value.
g. Click the Communication tab. See Figure 82
.
Figure 82 - Message Configuration Screen - Communications Tab