Troubleshooting Chapter 6
I/O Faults and Alarms
The table below contains a list of I/O-specific faults and alarms, the type of fault
or alarm, the action taken when the drive faults, the parameter used to configure
the fault or alarm (if applicable), and a description and action (where applicable).
Table 18 - I/O Fault and Alarm Types, Descriptions and Actions
Safe Torque Off Fault
The table below lists the safe torque off-specific fault, the action taken when the
drive faults, and its description.
Table 19 - Safe Torque Fault and Alarm Types, Descriptions and Actions
Event
No.
(1)
Fault/Alarm Text Type Fault
Action
Configuration
Parameter
Auto
Reset
Description/Action(s)
xx000 No Entry
xx001 Analog In Loss Configurable P53/P63
[Anlg InX LssActn]
Analog input has a lost signal.
xx002 Motor PTC Trip Configurable P40
[PTC Cfg]
Motor PTC (Positive Temperature Coefficient) over temperature.
xx005 Relay0 Life Configurable P106
[RO0 LifeEvntActn]
Predictive maintenance.
xx006 Relay1 Life Configurable P116
[RO1 LifeEvntActn]
Predictive maintenance.
xx010 Anlg Cal Chksum Non-Reset
Fault
Coast The checksum read from the analog calibration data does not match the
checksum calculated. Replace option module.
xx058 Module Defaulted Fault Coast Module was commanded to write default values.
(1) xx indicates the port number. Refer to Fault and Alarm Display Codes on page 312 for an explanation.
Event
No.
(1)
Fault/Alarm Text Type Fault
Action
Configuration
Parameter
Auto
Reset
Description/Action(s)
xx000 No Entry
xx058 Module Defaulted Fault Coast Module was commanded to write default values.
(1) xx indicates the port number. Refer to Fault and Alarm Display Codes on page 312 for an explanation.