Rockwell Automation Publication 750-PM001J-EN-P - October 2014 307
Troubleshooting Chapter 6
Drive Status Indicators
The condition or state of the drive is constantly monitored and is indicated
through the LEDs and/or the HIM (if present).
Table 6 - PowerFlex 753 Drive Status Indicator Descriptions
The Status Indicator LEDs on the HIM cradle do not indicate the current status
of an installed Communication Adapter option. If an optional Communication
Adapter is installed, refer to that option’s user manual for a description of LED
location and indication.
Name Color State Description
STS
(Status)
Green Flashing Drive ready but not running, and no faults are present.
Steady Drive running, no faults are present.
Yellow Flashing Drive is not running, a start inhibit condition exists and the drive cannot be started.
See parameter 933
[Start Inhibits].
Steady A type 1 (user configurable) alarm exists. If the drive is stopped, it is prevented from
starting until the alarm condition is cleared. If the drive is running, it continues to
run but cannot restart until the alarm condition is cleared.
See parameters 959
[Alarm Status A] and 960 [Alarm Status B].
Red Flashing A major fault has occurred. Drive will stop. Drive cannot be started until fault
condition is cleared. See parameter 951
[Last Fault Code].
Steady A non-resettable fault has occurred.
Red /
Yellow
Flashing
Alternately
A minor fault has occurred. When running, the drive continues to run. System is
brought to a stop under system control. Fault must be cleared to continue. Use
parameter 950
[Minor Flt Cfg] to enable. If not enabled, acts like a major fault.
Yellow /
Green
Flashing
Alternately
When running, a type 1 alarm exists.
See parameters 959 [Alarm Status A] and 960 [Alarm Status B].
Green /
Red
Flashing
Alternately
Drive is flash updating.