Rockwell Automation Publication 750-PM001J-EN-P - October 2014 317
Troubleshooting Chapter 6
102 NVS Not Blank Resettable
Fault
Coast Internal data error.
103 PwrDn NVS Incomp Resettable
Fault
Coast Internal data error.
104 Pwr Brd Checksum Non-Reset
Fault
The checksum read from the non-volatile storage does not match the
checksum calculated. Data set to default value.
106 Incompat MCB-PB Non-Reset
Fault
Coast The main control board did not recognize the power structure. Flash
with newer Application version.
107 Replaced MCB-PB Resettable
Fault
Coast The main control board was moved to a different power structure. Data
set to default values.
108 Anlg Cal Chksum Non-Reset
Fault
Coast The checksum read from the analog calibration data does not match the
checksum calculated. Replace main control board.
110 Ivld Pwr Bd Data Non-Reset
Fault
Coast Power structure data invalid.
• Verify ribbon cable connection between the main control board and
the power interface board.
• Replace power interface board.
111 PwrBd Invalid ID Non-Reset
Fault
Coast Power structure ID invalid.
• Verify ribbon cable connection between the main control board and
the power interface board.
• Replace power interface board.
112 PwrBd App MinVer Resettable
Fault
Coast Power structure needs newer Application version. Flash with newer
Application version.
113 Tracking DataErr Resettable
Fault
Coast Internal data error.
115 PwrDn Table Full Resettable
Fault
Coast Internal data error.
116 PwrDnEntry2Large Resettable
Fault
Coast Internal data error.
117 PwrDn Data Chksm Resettable
Fault
Coast Internal data error.
118 PwrBd PwrDn Chks Resettable
Fault
Coast Internal data error.
124 App ID Changed Resettable
Fault
Coast Application Firmware changed. Verify Application version.
125 Using Backup App Resettable
Fault
Coast Application did not flash correctly. Reflash.
134 Start On PowerUp Alarm 1 When P345 [Start At PowerUp] is enabled, an alarm will be set for the
time programmed in P346 [PowerUp Delay].
137 Ext Prechrg Err Configurable 323
[Prchrg Err Cfg] The seal contact on the external precharge contactor has opened (as
signalled by P190 [DI Prchrg Seal]) while the drive was running (PWM
was active).
138 Precharge Open Resettable
Fault
Coast 321
[Prchrg Control]
190
[DI Prchrg Seal]
189
[DI Precharge]
The internal precharge was commanded to open while the drive was
running (PWM was active). The internal fault latch will be automatically
cleared when PWM is disabled.
141 Autn Enc Angle Resettable
Fault
Coast P78 [Encdrlss AngComp] is out of range.
142 Autn Spd Rstrct Resettable
Fault
Coast Frequency limit settings are preventing the drive from reaching a
suitable speed during an Inertia Tune test.
143 Autotune CurReg Resettable
Fault
Coast Calculated values for P96 [VCL Cur Reg Kp] and/or P97 [VCL Cur Reg Ki]
are out of range.
144 Autotune Inertia Resettable
Fault
Coast Results from the Inertia Tune test out of range for P76 [Total Inertia].
145 Autotune Travel Resettable
Fault
Coast When P77 [Inertia Test Lmt] is set, the Inertia Tune test was prevented
from reaching a suitable speed to run the test.
Event
No.
Fault/Alarm Text Type Fault
Action
Configuration
Parameter
Auto
Reset
Description/Action(s)