468 Rockwell Automation Publication 750-PM001J-EN-P - October 2014
Appendix B Application Notes
Figure 77 - DriveObserver Settings
The value of P970 [Testpoint Sel 1] is referenced from P972 [Testpoint
Lval 1].
5. Set P970 [Testpoint Sel 1] to 2043. This is the cycle count.
Initialize the Pump Off Feature
1. Set P1190 [Pump Off Control] to option 1 “Baseline Set.
2. With the well full, start the drive.
You can see waveforms similar to the waveforms in Figure 77
. Monitor the
Pump Jack and verify the Pump Off Action.