B-9
EtherNet/IP Communications Module
Sets the Reference data that is sent to the drive if any of the
following is true:
Comm Flt Action (21) is set to Send Flt Cfg and communications
are disrupted.
Idle Flt Action (22) is set to Send Flt Cfg and the scanner is put
into Program mode.
Peer Flt Action (41) is set to Send Flt Cfg and communications
are disrupted.
Important: If the drive uses a 16-bit Reference, the most significant
word of this value must be set to zero (0) or a fault will
occur.
Sets the data that is sent to the Datalink in the drive if any of the
following is true:
Comm Flt Action (21) is set to Send Flt Cfg and communications
are disrupted.
Idle Flt Action (22) is set to Send Flt Cfg and the scanner is idle.
Peer Flt Action (41) is set to Send Flt Cfg and communications
are disrupted.
Important: If the drive uses a 16-bit Reference, the most significant
word of this value must be set to zero (0) or a fault will
occur.
26 Flt Cfg Ref
Range: 0 to 4294967295
Default: 0
Type: Read/Write
Reset Required: No
27
28
29
30
31
32
33
34
Flt Cfg A1
Flt Cfg A2
Flt Cfg B1
Flt Cfg B2
Flt Cfg C1
Flt Cfg C2
Flt Cfg D1
Flt Cfg D2
Range: 0 to 4294967295
Default: 0
Type: Read/Write
Reset Required: No