Getting Started
2-3
2.2 Installation Checklist
This section is designed to help experienced users start using the
EtherNet/IP module. If you are unsure how to complete a step, refer
to the referenced chapter.
Step Action Refer to:
1 Review the safety precautions for the
module.
Throughout
this manual
2 Verify that the drive is properly installed.
Drive User
Manual
3Install the module.
Verify that the drive and the network are not
powered. Then, connect the module to the
network using an Ethernet cable and to the
drive using the Internal Interface cable. Use
the captive screws to secure and ground
the module to the drive.
Chapter 3,
Installing the
EtherNet/IP
module
4 Apply power to the module.
Apply power to the network and to the drive.
The module receives power from the drive
and network. The status indicators should
be green. If they flash red, there is a
problem. Refer to chapter 8 for more
information on the status indicators.
Chapter 3,
Installing the
EtherNet/IP
module
5 Configure the module for your
application.
Set the parameters for the following
features as required by your application:
IP address, subnet mask, and gateway
address
Data rate
I/O configuration
Master-slave or peer-to-peer hierarchy
Fault actions
Chapter 4,
Configuring the
EtherNet/IP
module
6 Configure the scanner or bridge to
communicate with the module.
Use a software tool, such as RSLogix, to
configure the master on the EtherNet/IP
network to recognize the module and the
drive.
Chapter 5,
Configuring the
Scanner or
Bridge