
4-14
EtherNet/IP Communications Module
Step 2. In module parameters 42 through 45 (Peer Inp Addr 1
through Peer Inp Addr 4), set the IP address of the node
from which you want to receive data. See figure 4.20.
Valid nodes must have EtherNet/IP modules connected to
drives with compatible logic command/status words.
Step 3. Select the destination of the data that is input to the drive
as Peer A in module parameter 38 (Peer A Input). See
figure 4.21.
If you select a Reference or Datalink as an input, note the
following:
• If a drive that uses a 32-bit Reference and 32-bit
Datalinks receives a 16-bit Reference or Datalink, it
uses the data in its most significant word, and its least
significant word is zero.
Figure 4.19 – Peer Input Enable Screen on an LCD OIM
Figure 4.20 – Peer Input Address 1 Screen on an LCD OIM
Figure 4.21 – Peer A Input Screen on an LCD OIM
Value Setting
0 Off (Default)
1On
Port 5 Device
RECOMM-ENET
Parameter #: 47
Peer Inp Enable
0
Off
Port 5 Device
RECOMM-ENET
Parameter #: 42
Peer Inp Addr 1
0
0 <> 255
Default = 0.0.0.0
255 . 255 . 255 . 255
[Peer Inp Addr 1]
[Peer Inp Addr 2]
[Peer Inp Addr 3]
[Peer Inp Addr 4]
IP Address of Node Transmitting
Peer I/O
Port 5 Device
RECOMM-ENET
Parameter #: 38
Peer A Input
1
Cmd/Ref
Value Description
0 Off (Default)
1 Logic Command/Reference
2 - 5 Datalink A, B, C, or D
Input
Comentarios a estos manuales