B-14
EtherNet/IP Communications Module
Enables or disables the Peer I/O input.
Displays the status of the consumed peer input connection.
Selects the source of the Peer I/O output data. The module
transmits this data to the network.
Important: Changes to these parameters are ignored when Peer
Out Enable (51) is On.
47 Peer Input Enable
Range: 0 = Off
1 = On
Default: 0 = Off
Type: Read/Write
Reset Required: No
48 Peer Inp Status
Range: 0 = Off
1 = Waiting
2 = Running
3 = Faulted
Default: 0 = Off
Type: Read Only
Reset Required: N/A
49
50
Peer A Output
Peer B Output
Range: 0 = Off
1 = Cmd/Ref
2 = Datalink A Input
3 = Datalink B Input
4 = Datalink C Input
5 = Datalink D Input
6 = Datalink A Output
7 = Datalink B Output
8 = Datalink C Output
9 = Datalink D Output
Default: 0 = Off
Type: Read/Write
Reset Required: No