Vista de pagina 159
C-24
EtherNet/IP Communications Module
Formulas for Converting
Display Value = ((Internal Value + Offset) x Multiplier x Base) / (Divisor x 10
Decimal Places
)
Internal Value =
((
Display Value x Divisor x 10
Decimal Place)
/
(Multiplier x Base))
-
Offset
Common Services
Object Specific Services
21 Formula Links Reserved
22 Access Level (Bit 1) Reserved
23 Access Level (BIt 2) Reserved
24 Access Level (Bit 3) Reserved
25 Writable ENUM Reserved
26 Not a Link Source 0 = Parameter can be a source for a link
1 = Parameter cannot be a source for a link
27 Enhanced Bit ENUM Reserved
28 Enhanced ENUM Reserved
29 Not Used Reserved
30 Not Used Reserved
31 Not Used Reserved
Bit Name Description
Service
Code
Implemented for:
Service NameClass Instance
0x0E Yes Yes Get_Attribute_Single
0x10 Yes Yes Set_Attribute_Single
Service
Code
Implemented for:
Service NameClass Instance
0x4B Yes No Get_Attributes_Scattered
0x4C Yes No Set_Attributes_Scattered