EtherNet I/P Objects
C-25
C.9 DPI Fault Object
Class Code
Products such as SP600, GV6000 and LiquiFlo 2.0 drives use this
object for faults. Modules use this object for events.
Instances
The number of instances depends on the maximum number of
faults or events supported in the queue. The maximum number of
faults/events can be read in Instance 0, Attribute 2.
Class Attributes
Hexadecimal Decimal
0x97 151
Instances (Hex) (Dec) Device Example Description
0x0000-0x3FFF 0-16383 Host 0 Class Attributes (Drive)
0x4000-0x43FF 16384-17407 Module 1 Most Recent Drive Fault
0x4400-0x47FF 17408-18431 DPI Port 1 2 Second Most Recent
Drive Fault
0x4800-0x4BFF 18432-19455 DPI Port 2
...
...
0x4C00-0x4FFF 19456-20479 DPI Port 3 16384 Class Attributes (Module)
0x5000-0x53FF 20480-21503 DPI Port 4 16385 Most Recent Module
Event
0x5400-0x57FF 21504-22527 DPI Port 5
...
...
0x5800-0x5BFF 22528-23551 DPI Port 6
Attribute
ID
Access
Rule Name Data Type Description
1 Get Class Revision WORD Revision of object
2 Get Number of
Instances
WORD Maximum number of faults/events
that the device can record in its
queue
3 Set Fault Command
Write
BYTE 0 = No Operation
1 = Clear Fault/Event
2 = Clear Fault/Event Queue
3 = Reset Device
4 Get Fault Trip
Instance Read
WORD Fault that tripped the device. For
modules, this value is always 1
when faulted.