Rockwell Automation Publication 193-UM015B-EN-P - June 2014 107
Protective Trip and Warning Functions Chapter 5
Table 91 - Current Imbalance Trip Level (Parameter 261)
Current Imbalance Warning
The E300 Electronic Overload Relay will indicate a current imbalance warning
if:
No warning currently exists
Current Imbalance Warning is enabled
Current is present
Current Imbalance Inhibit Time has expired
The current imbalance (parameter 52) is greater than the Current
Im
balance Warning Level
When the Current Imbalance Warning conditions are satisfied, the:
T
RIP/WARN LED will flash a yellow 7-short blink pattern
Bit 6 in Current Warning Status (Parameter 10) will set to 1
Bit 1 in Device Status 0 (Parameter 20) will set to 1
Any relay outputs configured as a Warning Alarm will close
Current Imbalance Warning Level
Current Imbalance Warning Level (Parameter 262) allows the user to define the
percentage at which the E300 Electronic Overload Relay will indicate a warning.
It is user-adjustable from 10…100%.
Default Value 35
Minimum Value 10
Maximum Value 100
Parameter Type USINT
Size (Bytes) 1
Scaling Factor 1
Units %
IMPORTANT
The Current Imbalance Inhibit Timer starts after a phase of load current
transitions from 0A to 30% of the devices minimum FLA setting. The E300
Electronic Overload Relay does not begin monitoring for a current imbalance
condition until the Current Imbalance Inhibit Time expires.