168 Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Chapter 5 Protective Trip and Warning Functions
Table 164 - Over kVAR Consumed Trip Level (Parameter 392)
Over kVAR Consumed Warning
The E300 Electronic Overload Relay will indicate an Over kVAR warning if:
No warning currently exists
Over kVAR Consumed Warning is enabled
Current is present
Voltage is present
Over kVAR Consumed Inhibit Time has expired
The total reactive power (kVAR) consumed is equal to or greater than the
O
v
er kVAR Consumed Warning Level
When the Over kVAR Consumed Warning conditions are satisfied, the:
TRIP/WARN LED will flash a yellow 2-long / 4-short blink pattern
Bit 3 in Power Warning Status (Parameter 12) will set to 1
Bit 1 in Device Status 0 (Parameter 20) will set to 1
Any relay outputs configured as a Warning Alarm will close
Over kVAR Consumed Warn Level
Over kVAR Consumed Warn Level (Parameter 393) allows the user to define the
reactive power (kVAR) consumed at which the E300 Electronic Overload Relay
will indicate a warning. It is user-adjustable from 0…2,000,000 kW.
Table 165 - Over kVAR Consumed Warn Level (Parameter 393)
Default Value 0.000
Minimum Value 0.000
Maximum Value 2000000.000
Parameter Type DINT
Size (Bytes) 4
Scaling Factor 1000
Units kVAR
IMPORTANT
The Over kVAR Consumed Inhibit Time starts after a phase voltage transitions
from 0V to 20V L-L and a phase of load current transitions from 0A to 30% of
the devices minimum FLA setting. The E300 Electronic Overload Relay does not
begin monitoring for an over reactive power (kVAR) consumed condition until
the Over kVAR Consumed Inhibit Time expires.
Default Value 0.000
Minimum Value 0.000
Maximum Value 2000000.000
Parameter Type DINT
Size (Bytes) 4
Scaling Factor 1000
Units kVAR