118 Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Chapter 5 Protective Trip and Warning Functions
• Current is present
• Over Current Inhibit Timer has expired
• L1 Percent FLA (Parameter 47) is greater than the L1 Over Current Trip
Le
vel for a time period greater than the L1 Over Current Trip Delay.
If the E300 Electronic Overload Relay trips on a L1 Over Current, the:
• TRIP/WARN LED status indicator will flash a red 11-short blink pattern
• Bit 10 in Current Trip Status (Parameter 4) will set to 1
• Bit 0 in Device Status 0 (Parameter 20) will set to 1
• Any relay outputs configured as a Trip Relay will open
• Any relay outputs configured as a Control Relay will open
• Any relay outputs configured as a Trip Alarm will close
• Any relay outputs configured as a Normal Relay will be placed in their
P
r
otection Fault state (if so programmed)
L1 Over Current Trip Delay
L1 Over Current Trip Delay (Parameter 276) allows the installer to define the
time period a L1 Over Current condition must be present before a trip occurs. It
is adjustable from 0.1…25.0 seconds.
The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output
Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and
Digital Module 4 Output Relays are defined by the respective parameters:
• Output PT00 Protection Fault Action (Parameter 304)
• Output PT00 Protection Fault Value (Parameter 305)
• Output PT01 Protection Fault Action (Parameter 310)
• Output PT01 Protection Fault Value (Parameter 311)
• Output PT02 Protection Fault Action (Parameter 316)
• Output PT02 Protection Fault Value (Parameter 317)
• Output Digital Module 1 Protection Fault Action (Parameter 322)
• Output Digital Module 1 Protection Fault Value (Parameter 323)
• Output Digital Module 2 Protection Fault Action (Parameter 328)
• Output Digital Module 2 Protection Fault Value (Parameter 329)
• Output Digital Module 3 Protection Fault Action (Parameter 334)
• Output Digital Module 3 Protection Fault Value (Parameter 335)
• Output Digital Module 4 Protection Fault Action (Parameter 340)
• Output Digital Module 4 Protection Fault Value (Parameter 342)