Rockwell Automation Publication 193-UM015B-EN-P - June 2014 319
Troubleshooting Chapter 10
Resetting a Trip
The E300 Electronic Overload Relay trip condition can be reset by taking one of
the following actions:
• Actuating the Blue Trip/Reset button on the E300 Electronic Overload
Relay Communication Module
• A
ctuating the Reset button on the E300 Electronic Overload Relay
Op
erator Station
• Setting the Trip Reset bit in the E300 Electronic Overload Relay’s Output
Asse
mbly via the communications network
• Actuating a reset signal to one of the assigned digital inputs
Power
Under kW 2 1
Over kW 2 2
Under kVAR Consumed 2 3
Over kVAR Consumed 2 4
Under kVAR Generated 2 5
Over kVAR Generated 2 6
Under kVA 2 7
Over kVA 2 8
Under PF Lagging 2 9
Over PF Lagging 2 10
Under PF Leading 2 11
Over PF Leading 2 12
Control
Test 3 1
PTC 3 2
DeviceLogix 3 3
Operator Station 3 4
Remote Trip 3 5
Blocked Start 3 6
Hardware Fault 3 7
Configuration 3 8
Option Match 3 9
Feedback Timeout 3 10
Expansion Bus 3 11
Number Of Starts 3 12
Operating Hours 3 13
Non-Volatile Memory 3 14
Test Mode 3 15
Code Long Blink Pattern Short Blink Pattern
ATTENTION: Resetting a trip will not correct the cause for the trip. Corrective
action should be taken before resetting the trip.