238 Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Chapter 7 Metering and Diagnostics
Mismatch Status
Mismatch Status (Parameter 40) reports the module that is causing a mismatch
trip or warning in the E300 Electronic Overload Relay. Refer to Chapter 3
for
more information on a mismatch fault.
Table 245 - Mismatch Status (Parameter 40)
Current Monitor
The E300 Electronic Overload Relay current monitor diagnostics provides
information on the current consumed by the load that the E300 Electronic
Overload Relay is monitoring, and it provides diagnostics for a three phase
current system including imbalance and ground fault current.
L1 Current
L1 Current (Parameter 43) reports the current in Amperes flowing through the
L1 and T1 power terminals of the E300 Electronic Overload Relay Sensing
Module.
Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Function
0Match
Control Module
1 Mismatch
0Match
Sensing Module
1 Mismatch
0Match
Communication
Module
1 Mismatch
0Match
Operator Station
1 Mismatch
0Match
Digital Module 1
1 Mismatch
0Match
Digital Module 2
1 Mismatch
0Match
Digital Module 3
1 Mismatch
0Match
Digital Module 4
1 Mismatch
0Match
Analog Module 1
1 Mismatch
0Match
Analog Module 2
1 Mismatch
0Match
Analog Module 3
1 Mismatch
0Match
Analog Module 4
1 Mismatch