336 Rockwell Automation Publication 193-UM015B-EN-P - November 2013
Appendix B Parameter List
Device Monitor
(continued)
27 AnalogModuleID Expansion Bus Analog Module
Typ es
UINT 2 1 Bit0= AnalogMod1[0]
Bit1= AnalogMod1[1]
Bit2= AnalogMod2[0]
Bit3= AnalogMod2[1]
Bit4= AnalogMod3[0]
Bit5= AnalogMod3[1]
Bit6= AnalogMod4[0]
Bit7= AnalogMod4[1]
0
28 OperatingTime Time unit has been powered on UINT 2 1 0 65535 0 Hrs
29 StartsCounter Number of starts UINT 2 1 0 65535 0
30 Starts Available Number of Starts Available USINT 1 1 0 120 0
31 TimeToStart The Time to Start UINT 2 1 0 3600 0 Sec
32 Year Virtual RTC Year UINT 2 1 0 9999 0
33 Month Virtual RTC Month UINT 2 1 0 12 0
34 Day Virtual RTC Day UINT 2 1 0 31 0
35 Hour Virtual RTC Hour UINT 2 1 0 23 0
36 Minute Virtual RTC Minute UINT 2 1 0 59 0
37 Second Virtual RTC Second UINT 2 1 0 59 0
38 InvaldCfgParam Number of incorrectly configured
parameter
UINT 2 1 0 9999 0
39 InvaldCfgCause Description of error USINT 1 1 0=NoError
1=ValueOverMax
2=Value UnderMin
3=IllegalValue
4=L3CurrentDetected
5=CopyCat Error
6-50 = Reserved
0
40 Reserved
41 Reserved
42 Reserved
Current Monitor 43 L1Current The actual L1 Phase Current. DINT 4 100 0 2000000000 0 Amps
44 L2Current The actual L2 Phase Current. DINT 4 100 0 2000000000 0 Amps
45 L3Current The actual L3 Phase Current. DINT 4 100 0 2000000000 0 Amps
46 AverageCurrent Average of Phase Currents. DINT 4 100 0 2000000000 0 Amps
47 L1PercentFLA L1 Current in %FLA UINT 2 10 0 10000 0 %
48 L2PercentFLA L2 Current in %FLA UINT 2 10 0 10000 0 %
49 L3PercentFLA L3 Current in %FLA UINT 2 10 0 10000 0 %
50 AvgPercentFLA Average Current in %FLA UINT 2 10 0 10000 0 %
51 GFCurrent The Ground Fault Current. UINT 2 100 0 9999 0 Amps
52 CurrentImbal Percent Current Imbalance USINT 1 1 0 200 0 %
Voltage Monitor 53 L1toL2Voltage 3 Phase RMS Voltage Line-Line UINT 2 10 0 65535 0 Volt
54 L2toL3Voltage 3 Phase RMS Voltage Line-Line UINT 2 10 0 65535 0 Volt
55 L3toL1Voltage 3 Phase RMS Voltage Line-Line UINT 2 10 0 65535 0 Volt
56 AvgVoltageLtoL Average RMS Voltage Line-Line UINT 2 10 0 65535 0 Volt
57 L1toNVoltage 3 Phase RMS Voltage Line-
Neutral
UINT 2 10 0 65535 0 Volt
58 L2toNVoltage 3 Phase RMS Voltage Line-
Neutral
UINT 2 10 0 65535 0 Volt
59 L3toNVoltage 3 Phase RMS Voltage Line-
Neutral
UINT 2 10 0 65535 0 Volt
Group
Param
No.
Parameter Name Description Type
Data Size
(bytes)
Scale
Factor
Min Max Default Units