Vista de pagina 347
348 Rockwell Automation Publication 193-UM015B-EN-P - November 2013
Appendix B Parameter List
Device Setup
(continued
201 InPt05Assignment Assignment for Input Point 05
function
USINT 1 1 0=Normal
1=TripReset
2=RemoteTrip
3=ActivateFLA2
4=ForceSnapshot
5=EmergencyStart
6=TestMode
7=L1LossArm
8=L2LossArm
9=L3LossArm
10=L1L2LossArm
11=L2L3LossArm
12=L1L3LossArm
13=L1L2L3LossArm
0
202 OutPt0Assignment Assignment for OutputPt00
function
USINT 1 1 0=Normal
1=TripRelay
2=ControlRelay
3=TripAlarm
4=WarningAlarm
5=MonL1TripRelay
6= MonL2TripRelay
7= MonL3TripRelay
1
203 OutPt1Assignment Assignment for OutputPt01
function
USINT 1 1 0=Normal
1=TripRelay
2=ControlRelay
3=TripAlarm
4=WarningAlarm
5=MonL1TripRelay
6= MonL2TripRelay
7= MonL3TripRelay
0
204 OutPt2Assignment Assignment for OutputPt02
function
USINT 1 1 0=Normal
1=TripRelay
2=ControlRelay
3=TripAlarm
4=WarningAlarm
5=MonL1TripRelay
6= MonL2TripRelay
7= MonL3TripRelay
0
205 StartsPerHour Allowable Starts per Hour USINT 1 1 0 120 2
206 StartsInterval The minimum allowable interval
between starts
UINT 2 1 0 3600 600 Sec
207 PMTotalStarts Total number of starts for
preventative maintenance
UINT 2 1 0 65535 0
208 PMOperatingHours Total operating hours for
preventative maintenance
UINT 2 1 0 65535 0 Hrs
209 ActFLA2wOutput Select FLA2 activate source USINT 1 1 0=Disable
1=OutputPt00
2=OutputPt01
3=OutputPt02
0
210 Reserved
Group
Param
No.
Parameter Name Description Type
Data Size
(bytes)
Scale
Factor
Min Max Default Units
Vista de pagina 347