302 Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Chapter 8 EtherNet/IP Communications
2. Select the Generic Ethernet Module, then click Create.
3. Enter a name and the IP address for the E300 Electronic Overload Relay
Et
herNet/IP Communication Module. The name will create tags in
RSLogix 5000 or Studio 5000 that can be used to read and write data from
the E300 Electronic Overload Relay EtherNet/IP Communication
Module.
4. Select Data-DINT for the Comm Format. The Data-DINT format will
re
present the data from the EtherNet/IP Communications Auxiliary E300
Electronic Overload Relay EtherNet/IP Communication Module as a
collection of 32-bit values. Set the I/O Assemblies to the following values:
Input Assembly Instance 199 (Size 39)
Output Assembly Instance 144 (Size 2)
Configuration Assembly Instance 120 (Size 0)