84 Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Chapter 5 Protective Trip and Warning Functions
Automatic/Manual Reset
Overload Reset Mode (Parameter 173) allows the user to select the reset mode
for the E300 Electronic Overload Relay after an overload or thermistor (PTC)
trip. If an overload trip occurs and automatic reset mode is selected, the E300
Electronic Overload Relay will automatically reset when the value stored in %
Thermal Capacity Utilized (Parameter 1) falls below the value stored in
Overload Reset Level (Parameter 174). If manual reset mode is selected, the
E300 Overload Relay can be manually reset after the % Thermal Capacity
Utilized is less than the OL Reset Level.
Table 62 - Overload Reset Mode (Parameter 173)
Table 63 - Overload Reset Level (Parameter 174)
Overload Reset Mode (Parameter 173)
Default Value 0 = Manual
Minimum Value 0 = Manual
Maximum Value 1 = Automatic
Parameter Type BOOL
Size (Bytes) 1
Scaling Factor 1
Units
Overload Reset Level (Parameter 174)
Default Value 75
Minimum Value 0
Maximum Value 100
Parameter Type USINT
Size (Bytes) 1
Scaling Factor 1
Units %TCU