Rockwell Automation Publication 193-UM015B-EN-P - June 2014 169
Protective Trip and Warning Functions Chapter 5
Under kVAR Generated Trip
The E300 Electronic Overload Relay will trip with an Under kVAR Generated
indication if:
• No trip currently exists
• Under kVAR Generated Trip is enabled
• Current is present
• Voltage is present
• Under kVAR Generated Inhibit Time has expired
• The total reactive power (kVAR) gen
e
rated is less than the Under
• kVAR Generated Trip Level for a time period greater than the Under
kV
AR Generated Trip Delay.
If the E300 Electronic Overload Relay trips on an under reactive power (kVAR)
gene
rated, the:
• T
RIP/WARN LED status indicator will flash a red 2-long / 5-short blink
pa
ttern
• Bit 4 in Power Trip Status (Parameter 6) will set to 1
• Bit 0 in Device Status 0 (Parameter 20) will set to 1
• Any relay outputs configured as a Trip Relay will open
• Any relay outputs configured as a Control Relay will open
• Any relay outputs configured as a Trip Alarm will close
• Any relay outputs configured as a Normal Relay will be placed in their
P
r
otection Fault state (if so programmed)
The Over kVAR Consumed Warning function does not include a time delay
feature. Once the Over kVAR Consumed Inhibit Time has expired, the Over kVAR
Consumed Warning indication is instantaneous.