338 Rockwell Automation Publication 193-UM015B-EN-P - November 2013
Appendix B Parameter List
Energy
Monitoring
(Continued)
95 kVARhNet10E9 Total Reactive Energy Net
(kVARh) Word 10^9
INT 2 1 -999 999 0
96 kVARhNet10E6 Total Reactive Energy Net
(kVARh) Word 10^6
INT 2 1 -999 999 0
97 kVARhNet10E3 Total Reactive Energy Net
(kVARh) Word 10^3
INT 2 1 -999 999 0
98 kVARh Net 10E0 Total Reactive Energy Net
(kVARh) Word 10^0
INT 2 1 -999 999 0
99 kVARhNet10E-3 Total Reactive Energy Net
(kVARh) Word 10^-3
INT 2 1 -999 999 0
100 kVAhTimes10E9 Total Apparent Energy (kVAh)
Word 10^9
INT 2 1 -999 999 0
101 kVAhTimes10E6 Total Apparent Energy (kVAh)
Word 10^6
INT 2 1 -999 999 0
102 kVAhTimes10E3 Total Apparent Energy (kVAh)
Word 10^3
INT 2 1 -999 999 0
103 kVAhTimes10E0 Total Apparent Energy (kVAh)
Word 10^0
INT 2 1 -999 999 0
104 kVAhTimes10E-3 Total Apparent Energy (kVAh)
Word 10^-3
INT 2 1 -999 999 0
105 kWDemand Real Power Demand DINT 4 1000 -2000000000 2000000000 0 kW
106 MaxkWDemand Maximum Real Power Demand DINT 4 1000 -2000000000 2000000000 0 kW
107 VARDemand Reactive Power Demand DINT 4 1000 -2000000000 2000000000 0 kVAR
108 MaxVARDemand Maximum Reactive Demand DINT 4 1000 -2000000000 2000000000 0 kVAR
109 VADemand Apparent Power Demand DINT 4 1000 0 2000000000 0 kVA
110 MaxVADemand Maximum Apparent Power
Demand
DINT 4 1000 0 2000000000 0 kVA
Analog
Monitoring
111 InAnMod1Ch00 Value measured at Analog
Expansion Module 1 Input 00
UINT 2 1 0 65535 0
112 InAnMod1Ch01 Value measured at Analog
Expansion Module 1 Input 01
UINT 2 1 0 65535 0
113 InAnMod1Ch02 Value measured at Analog
Expansion Module 1 Input 02
UINT 2 1 0 65535 0
114 InAnMod2Ch00 Value measured at Analog
Expansion Module 2 Input 00
UINT 2 1 0 65535 0
115 InAnMod2Ch01 Value measured at Analog
Expansion Module 2 Input 01
UINT 2 1 0 65535 0
116 InAnMod2Ch02 Value measured at Analog
Expansion Module 2 Input 02
UINT 2 1 0 65535 0
117 InAnMod3Ch00 Value measured at Analog
Expansion Module 3 Input 00
UINT 2 1 0 65535 0
118 InAnMod3Ch01 Value measured at Analog
Expansion Module 3 Input 01
UINT 2 1 0 65535 0
119 InAnMod3Ch02 Value measured at Analog
Expansion Module 3 Input 02
UINT 2 1 0 65535 0
120 InAnMod4Ch00 Value measured at Analog
Expansion Module 4 Input 00
UINT 2 1 0 65535 0
121 InAnMod4Ch01 Value measured at Analog
Expansion Module 4 Input 01
UINT 2 1 0 65535 0
122 InAnMod4Ch02 Value measured at Analog
Expansion Module 4 Input 02
UINT 2 1 0 65535 0
Group
Param
No.
Parameter Name Description Type
Data Size
(bytes)
Scale
Factor
Min Max Default Units