210 Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Chapter 6 Commands
Table 209 - Config Preset (Parameter 164)
Listed below are the available configuration presets and the values for the
associated pre-configured configuration values.
Factory Defaults
When the Factory Defaults configuration preset command is selected, the E300
Electronic Overload Relay will restore all configuration parameters back their
original factory default values.
Figure 43 - Factory Default Values
Default Value 0 = Ready
Range 0 = Ready
1 = Factory Defaults
Parameter Type USINT
Size (Bytes) 1
Scaling Factor 1
Units
Number Parameter Name Default
Value
Units Number Parameter Name Default
Value
Units Number Parameter Name Default
Value
Units
139 TripHistoryMaskI 0xFFFF 304 OutPt00PrFltAct Goto
Value
428 Screen1Param1 1
140 TripHistoryMaskV 0x003F 305 OutPt00PrFltVal Open 429 Screen1Param2 50
141 TripHistoryMaskP 0x0FFF 306 OutPt00ComFltAct Goto
Value
430 Screen2Param1 2
142 TripHistoryMaskC 0x27FF 307 OutPt00ComFltVal Open 431 Screen2Param2 3
143 TripHistoryMaskA 0x0FFF 308 OutPt00ComIdlAct Goto
Value
432 Screen3Param1 51
145 WarnHistoryMaskI 0xFFFF 309 OutPt00ComIdlVal Open 433 Screen3Param2 52
146 WarnHistoryMaskV 0x003F 310 OutPt01PrFltAct Goto
Value
434 Screen4Param1 38
147 WarnHistoryMaskP 0x0FFF 311 OutPt01PrFltVal Open 435 Screen4Param2 39
148 WarnHistoryMaskC 0x1FFF 312 OutPt01ComFltAct Goto
Value
436 DisplayTimeout 300 Sec
149 WarnHistoryMaskA 0x0FFF 313 OutPt01ComFltVal Open 437 InAnMod1Ch00Type Disable
171 FLASetting 0.50 Amps 314 OutPt01ComIdlAct Goto
Value
438 InAMod1Ch0Format Eng Units
172 TripClass 10 315 OutPt01ComIdlVal Open 439 InAMod1C0TmpUnit Degrees C
173 OLPTCResetMode Automati
c
316 OutPt02PrFltAct Goto
Value
440 InAMod1C0FiltFrq 17 Hz
174 OLResetLevel 75 %TCU 317 OutPt02PrFltVal Open 441 InAMod1C0OpCktSt Upscale
175 OLWarningLevel 85 %TCU 318 OutPt02ComFltAct Goto
Value
442 InAnMod1Ch0RTDEn 3-Wire
176 SingleOrThreePh Three
Phase
319 OutPt02ComFltVal Open 443 InAMod1C0TripDly 1.0 Sec
177 FLA2Setting 0.50 Amps 320 OutPt02ComIdlAct Goto
Value
444 InAMod1C0TripLvl 0
183 TripEnableI 0x0003 321 OutPt02ComIdlVal Open 445 InAMod1C0WarnLvl 0