358 Rockwell Automation Publication 193-UM015B-EN-P - November 2013
Appendix B Parameter List
Diagnostic
Display Setup
(Continued)
435 Screen4Param2 Parameter to display on Operator
Station Startup screen 4 line 2
UINT 2 1 0 560 39
436 DisplayTimeout Inactivity time for a Diagnostic
Station
UINT 2 1 0 65535 300
Analog1 Setup 437 InAnMod1Ch00Type Assignment for Analog Module 1
Input Channel 00 function
USINT 1 1 0= Disabled
1= 4To20mA
2= 0To20mA
3= 0To10Volts
4= 1To5Volts
5= 0To5Volts
6= 100Pt385
7= 200Pt385
8= 500Pt385
9= 1000Pt385
10=100Pt3916
11= 200Pt3916
12= 500Pt3916
13= 1000Pt3916
14= 10Cu426
15= 120Ni618
16= 120Ni672
17= 604NiFe518
18= 150ohm
19= 1000ohm
20 = 3000ohm
21= 6000ohm
0
438 InAMod1Ch0Format Assignment for Analog Module 1
Input Channel 00 Data Format
USINT 1 1 0= EngUnits
1= EngUnitsTimes10
2= RawProportional
3= ScaledForPID
0
439 InAMod1C0TmpUnit Assignment for Analog Module 1
Input Channel 00 Temperature
Units
USINT 1 1 0=DegreesC
1=DegreesF
0
440 InAMod1C0FiltFrq Assignment for Analog Module 1
Input Channel 00 Filter Freq
USINT 1 1 0=17Hz
1=4Hz
2=62Hz
3=470Hz
0
441 InAMod1C0OpCktSt Indicates Analog Module 1 Input
Channel 00 Open Circuit State
USINT 1 1 0=Upscale
1=Downscale
2=Zero
0
442 InAnMod1Ch0RTDEn Enable Analog Module 1 Input
Channel 00 to function with RTD
BOOL 1 1 0=3-wire
1=2-wire
0
443 InAMod1C0TripDly Analog Module 1 Input Channel
00 Trip Delay
USINT 1 10 0 250 10 Sec
444 InAMod1C0TripLvl Level (in selected Units) where
Analog Input generates a trip
UINT 2 1 0 65535 0
445 InAMod1C0WarnLvl Level (in selected Units) where
Analog Input generates a
warning
UINT 2 1 0 65535 0
Group
Param
No.
Parameter Name Description Type
Data Size
(bytes)
Scale
Factor
Min Max Default Units