Rockwell Automation Publication 193-UM015B-EN-P - November 2013 361
Parameter List Appendix B
Analog1 Setup
(continued)
465 OutAnMod1Select Assignment of parameter data
value to drive Analog Module 1
Output
USINT 1 1 0= AveragePctFLA
1= ScaledAvgPctFLA
2= PercentTCU
3= GFCurrent
4= CurrentUnbalance
5= AvgLLVoltage
6=VoltLLUnbalance
7= TotalkW
8= TotalkVA
9= TotalkVAR
10= TotalPF
11= UserDLXData
0
466 OutAnMod1FltActn Analog Module 1 Output action
on comms fault
USINT 1 1 0= Zero
1= Maximum
2= Minimum
3= Hold Last State
0
467 OutAnMod1IdlActn Analog Module 1 Output action
on comms idle
USINT 1 1 0= Zero
1= Maximum
2= Minimum
3= Hold Last State
0
Analog2 Setup
468 InAnMod2Ch00Type Assignment for Analog Module 2
Input Channel 00 function
USINT 1 1 0= Disabled
1= 4To20mA
2= 0To20mA
3= 0To10Volts
4= 1To5Volts
5= 0To5Volts
6= 100Pt385
7= 200Pt385
8= 500Pt385
9= 1000Pt385
10=100Pt3916
11= 200Pt3916
12= 500Pt3916
13= 1000Pt3916
14= 10Cu426
15= 120Ni618
16= 120Ni672
17= 604NiFe518
18= 150ohm
19= 1000ohm
20 = 3000ohm
21= 6000ohm
0
469 InAMod2Ch0Format Assignment for Analog Module 2
Input Channel 00 Data Format
USINT 1 1 0= EngUnits
1= EngUnitsTimes10
2= RawProportional
3= ScaledForPID
0
470 InAMod2C0TmpUnit Assignment for Analog Module 2
Input Channel 00 Temperature
Units
USINT 1 1 0=DegreesC
1=DegreesF
0
471 InAMod2C0FiltFrq Assignment for Analog Module 2
Input Channel 00 Filter Freq
USINT 1 1 0=17Hz
1=4Hz
2=62Hz
3=470Hz
0
Group
Param
No.
Parameter Name Description Type
Data Size
(bytes)
Scale
Factor
Min Max Default Units