Analog1 Setup
(Continued)
455 InAnMod1Ch02Type Assignment for Analog Module 1
Input Channel 02 function
USINT 1 1 0= Disabled
1= 4To20mA
2= 0To20mA
3= 0To10Volts
4= 1To5Volts
5= 0To5Volts
6= 100Pt385
7= 200Pt385
8= 500Pt385
9= 1000Pt385
10=100Pt3916
11= 200Pt3916
12= 500Pt3916
13= 1000Pt3916
14= 10Cu426
15= 120Ni618
16= 120Ni672
17= 604NiFe518
18= 150ohm
19= 1000ohm
20 = 3000ohm
21= 6000ohm
0
456 InAMod1Ch2Format Assignment for Analog Module 1
Input Channel 02 Data Format
USINT 1 1 0= EngUnits
1= EngUnitsTimes10
2= RawProportional
3= ScaledForPID
0
457 InAMod1C2TmpUnit Assignment for Analog Module 1
Input Channel 02 Temperature
Units
USINT 1 1 0=DegreesC
1=DegreesF
0
458 InAMod1C2FiltFrq Assignment Analog Module 1
Input Channel 02 Filter Freq
USINT 1 1 0=17Hz
1=4Hz
2=62Hz
3=470Hz
0
459 InAMod1C2OpCktSt Indicates Analog Module 1 Input
Channel 02 Open Circuit State
USINT 1 1 0=Upscale
1=Downscale
2=Zero
0
460 InAnMod1Ch2RTDEn Enable Analog Module 1 Input
Channel 02 to function with RTD
BOOL 1 1 0=3-wire
1=2-wire
0
461 InAMod1C2TripDly Analog Module 1 Input Channel
02 Trip Delay
USINT 1 10 0 250 10 Sec
462 InAMod1C2TripLvl Level (in selected Units) where
Analog Input generates a trip
UINT 2 1 0 65535 0
463 InAMod1C2WarnLvl Level (in selected Units) where
Analog Input generates a
warning
UINT 2 1 0 65535 0
464 OutAnMod1Type Assignment for Analog Module 1
Output function
USINT 1 1 0= Disabled
1= 4To20mA
2= 0To20mA
3= 0To10Volts
4=1to5 Volts
5= 0to5 Volts
0
Group
Param
No.
Parameter Name Description Type
Data Size
(bytes)
Scale
Factor
Min Max Default Units
Comentarios a estos manuales