174 Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Chapter 5 Protective Trip and Warning Functions
Table 170 - Over kVAR Generated Trip Level (Parameter 400)
Over kVAR Generated Warning
The E300 Electronic Overload Relay will indicate an Over kVAR warning if:
No warning currently exists
Over kVAR Generated Warning is enabled
Current is present
Voltage is present
Over kVAR Generated Inhibit Time has expired
The total reactive power (kVAR) generated is equal to or greater than the
Ov
e
r kVAR Generated Warning Level
When the Over kVAR Generated Warning conditions are satisfied, the:
TRIP/WARN LED will flash a yellow 2-long / 6-short blink pattern
Bit 5 in Power Warning Status (Parameter 12) will set to 1
Bit 1 in Device Status 0 (Parameter 20) will set to 1
Any relay outputs configured as a Warning Alarm will close
Over kVAR Generated Warn Level
Over kVAR Generated Warn Level (Parameter 401) allows the user to define the
reactive power (kVAR) generated at which the E300 Electronic Overload Relay
will indicate a warning. It is user-adjustable from 0…2,000,000 kW.
Table 171 - Over kVAR Generated Warn Level (Parameter 401)
Default Value 0.000
Minimum Value 0.000
Maximum Value 2000000.000
Parameter Type DINT
Size (Bytes) 4
Scaling Factor 1000
Units kVAR
IMPORTANT
The Over kVAR Generated Inhibit Time starts after a phase voltage transitions
from 0V to 20V L-L and a phase of load current transitions from 0A to 30% of
the devices minimum FLA setting. The E300 Electronic Overload Relay does not
begin monitoring for an over reactive power (kVAR) generated condition until
the Over kVAR Generated Inhibit Time expires.
Default Value 0.000
Minimum Value 0.000
Maximum Value 2000000.000
Parameter Type DINT
Size (Bytes) 4
Scaling Factor 1000
Units kVAR