Rockwell-automation 592- E300 Overload Relay User Manual Manual de usuario Pagina 340

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 424
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 339
340 Rockwell Automation Publication 193-UM015B-EN-P - November 2013
Appendix B Parameter List
Analog
Monitoring
(Continued)
126 AnalogMod4Status Analog Expansion Module 4
Status
UINT 2 1 Bit0= InCh00OpenCrcuit
Bit1= InCh00OverRange
Bit2= InCh00UnderRange
Bit3= InCh01OpenCrcuit
Bit4= InCh01OverRange
Bit5= InCh01UnderRange
Bit6= InCh02OpenCrcuit
Bit7= InCh02OverRange
Bit8= InCh02UnderRange
Bit9= OutOpenCircuit
Bit10= OutHoldLastSt
Bit11= OutOverRange
Bit12= OutUnderRange
Bit 13=Module Configured
Bit 14=Module Warning
Bit 15=Module Faulted
0
Trip/Warn
History
127 TripHistory0 Last trip to occur UINT 2 1 See Trip History Codes 0
128 TripHistory1 Second last trip to occur UINT 2 1 See Trip History Codes 0
129 TripHistory2 Third last trip to occur UINT 2 1 See Trip History Codes 0
130 TripHistory3 Fourth last trip to occur UINT 2 1 See Trip History Codes 0
131 TripHistory4 Fifth last trip to occur UINT 2 1 See Trip History Codes 0
132 Reserved
133 WarningHistory0 Last warning to occur. UINT 2 1 See Warning History Codes 0
134 WarningHistor y1 Second last warning to occur. UINT 2 1 See Warning History Codes 0
135 WarningHistory2 Third last warning to occur. UINT 2 1 See Warning History Codes 0
136 WarningHistor y3 Fourth last warning to occur. UINT 2 1 See Warning History Codes 0
137 WarningHistory4 Fifth last warning to occur. UINT 2 1 See Warning History Codes 0
138 Reserved
139 TripHistoryMaskI Trip History Mask for Current
Based Trips
UINT 2 1 Bit0= OverloadTrip
Bit1= PhaseLossTrip
Bit2= GroundFaultTrip
Bit3= StallTrip
Bit4= JamTrip
Bit5= UnderloadTrip
Bit6= CurrentImbalTrip
Bit7= L1UnderCurrTrip
Bit8= L2UnderCurrTrip
Bit9= L3UnderCurrTrip
Bit10= L1OverCurrenTrip
Bit11= L2OverCurrenTrip
Bit12= L3OverCurrenTrip
Bit13= L1LineLossTrip
Bit14= L2LineLossTrip
Bit15= L3LineLossTrip
0xFFFF
140 TripHistoryMaskV Trip History Mask for Voltage
Based Trips
UINT 2 1 Bit0= UnderVoltageTrip
Bit1= OvervoltageTrip
Bit2= VoltageUnbalTrip
Bit3= PhaseRotationTrp
Bit4= UnderFreqTrip
Bit5= OverFreqTrip
0x3F
Group
Param
No.
Parameter Name Description Type
Data Size
(bytes)
Scale
Factor
Min Max Default Units
Vista de pagina 339
1 2 ... 335 336 337 338 339 340 341 342 343 344 345 ... 423 424

Comentarios a estos manuales

Sin comentarios