Chapter 5 Protective Trip and Warning Functions
Phase Loss Trip
The E300 Electronic Overload Relay will trip with a phase loss indication if:
No trip currently exists
Phase Loss Protection is enabled
Current is Present
Phase Loss Inhibit Time has expired
Current Imbalance is equal to or greater than 100% for a time period
g
r
eater than the programmed Phase Loss Trip Delay
If the E300 Electronic Overload Relay trips on a phase loss, the:
TRIP/WARN LED status indicator will flash a red short-2 blink pattern
Bit 1 in Current Trip Status (Parameter 4) will set to 1
Bit 0 of Device Status 0 (Parameter 20) will set to 1
Any relay outputs configured as a Trip Relay will open
Any relay outputs configured as a Control Relay will open
Any relay outputs configured as a Trip Alarm will close
Any relay outputs configured as a Normal Relay will be placed in their
P
r
otection Fault state (if so programmed)
IMPORTANT
The phase loss inhibit timer starts after the maximum phase of load current
transitions from 0 A to 30% of the devices minimum FLA Setting. The E300
Electronic Overload Relay does not begin monitoring for a phase loss condition
until the Phase Loss Inhibit Time expires.
IMPORTANT
The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output
Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and
Digital Module 4 Output Relays are defined by the respective parameters:
Output PT00 Protection Fault Action (Parameter 304)
Output PT00 Protection Fault Value (Parameter 305)
Output PT01 Protection Fault Action (Parameter 310)
Output PT01 Protection Fault Value (Parameter 311)
Output PT02 Protection Fault Action (Parameter 316)
Output PT02 Protection Fault Value (Parameter 317)
Output Digital Module 1 Protection Fault Action (Parameter 322)
Output Digital Module 1 Protection Fault Value (Parameter 323)
Output Digital Module 2 Protection Fault Action (Parameter 328)
Output Digital Module 2 Protection Fault Value (Parameter 329)
Output Digital Module 3 Protection Fault Action (Parameter 334)
Output Digital Module 3 Protection Fault Value (Parameter 335)
Output Digital Module 4 Protection Fault Action (Parameter 340)
Output Digital Module 4 Protection Fault Value (Parameter 342)