248 Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Chapter 7 Metering and Diagnostics
Table 270 - L2 Real Power (Parameter 65)
L3 Real Power
L3 Real Power (Parameter 66) reports the real power for line 3 in kW or MW
depending on the configuration value for Power Scale (Parameter 377). When
Voltage Mode (Parameter 352) is set to any Delta base setting, L3 Real Power is
set to 0. When Single or Three Phase (Parameter 176) is set to Single Phase, L3
Real Power is set to 0.
Table 271 - L3 Real Power (Parameter 66)
Total Real Power
Total Real Power (Parameter 67) reports the total real power of the monitored
power conductors in kW or MW depending on the configuration value for
Power Scale (Parameter 377). When Single or Three Phase (Parameter 176) is
set to Three Phase, Total Real Power is calculated as follows:
Total Real Power = (L1 Real Power + L2 Real Power + L3 Real Power)
When Single or Three Phase (Parameter 176) is set to Single Phase, Total Real
Power is calculated as follows:
Total Real Power = (L1 Real Power + L2 Real Power)
Default Value 0.000
Minimum Value -2000000.000
Maximum Value 2000000.000
Parameter Type DINT
Size (Bytes) 4
Scaling Factor 1000
Units kW or MW
Default Value 0.000
Minimum Value -2000000.000
Maximum Value 2000000.000
Parameter Type DINT
Size (Bytes) 4
Scaling Factor 1000
Units kW or MW