Rockwell-automation 592- E300 Overload Relay User Manual Manual de usuario Pagina 201

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 424
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 200
Rockwell Automation Publication 193-UM015B-EN-P - June 2014 201
Protective Trip and Warning Functions Chapter 5
Starts Interval
Starts Interval (Parameter 206) is the time that the user must wait between starts.
This value is adjustable from 0…3600 seconds.
Table 201 - Starts Interval (Parameter 206)
Starts Available
Starts Available (Parameter 30) reports the number of starts currently available
based on the blocked start settings and the actual motor starting events.
Table 202 - Starts Available (Parameter 30)
Time to Start
Time to Start (Parameter 31) reports the amount of the time remaining until a
new start can be issued. If the Time to Start time has elapsed, this parameter will
report zero until the next Blocked Start trip occurs.
Table 203 - Time to Start (Parameter 31)
Default Value 600
Minimum Value 0
Maximum Value 3600
Parameter Type UINT
Size (Bytes) 2
Scaling Factor 1
Units Sec
Default Value 0
Minimum Value 0
Maximum Value 120
Parameter Type USINT
Size (Bytes) 1
Scaling Factor 1
Units
Default Value 0
Minimum Value 0
Maximum Value 3600
Parameter Type UINT
Size (Bytes) 2
Scaling Factor 1
Units Sec
Vista de pagina 200
1 2 ... 196 197 198 199 200 201 202 203 204 205 206 ... 423 424

Comentarios a estos manuales

Sin comentarios