332 Rockwell Automation Publication 193-UM015B-EN-P - November 2013
Appendix B Parameter List
Device Monitor
(continued)
6 TripStsPower Trip Status bits for Power UINT 2 1 Bit0= UnderKWTrip
Bit1= OverKWTrip
Bit2= UnderKVARConTrip
Bit3= OverKVARConTrip
Bit4= UnderKVARGenTrip
Bit5= OverKVARGenTrip
Bit6= UnderKVATrip
Bit7= OverKVATrip
Bit8= UnderPFLagTrip
Bit9= OverPFLagTrip
Bit10= UnderPFLeadTrip
Bit11= OverPFLeadTrip
0
7 TripStsControl Trip Status bits for Control UINT 2 1 Bit0= TestTrip
Bit1= PTCTrip
Bit2= DLXTrip
Bit3= OperStationTrip
Bit4= RemoteTrip
Bit5= BlockedStartTrip
Bit6= HardwareFltTrip
Bit7= ConfigTrip
Bit8= OptionMatchTrip
Bit9= DLXFBTimeoutTrip
Bit10= ExpansionBusTrip
Bit11= Reserved
Bit12 =Reserved
Bit13= NVSTrip
Bit 14=TestMode Trip
0
8 TripStsAn alo g Trip Status bits for Analog UINT 2 1 Bit0= InAnMod1Ch00Trip
Bit1= InAnMod1Ch01Trip
Bit2= InAnMod1Ch02Trip
Bit3= InAnMod2Ch00Trip
Bit4= InAnMod2Ch01Trip
Bit5= InAnMod2Ch01Trip
Bit6= InAnMod3Ch00Trip
Bit7= InAnMod3Ch01Trip
Bit8= InAnMod3Ch02Trip
Bit9= InAnMod4Ch00Trip
Bit10= InAnMod4Ch01Trip
Bit11= InAnMod4Ch02Trip
0
9 Reserved
10 WarnStsCurrent Warning Status bits for Current UINT 2 1 Bit0= OverloadWarning
Bit1= Reserved
Bit2= GroundFltWarning
Bit3= Reserved
Bit4= JamWarning
Bit5= UnderloadWarning
Bit6= CurrentImbalWarn
Bit7= L1UnderCurrWarn
Bit8= L2UnderCurrWarn
Bit9= L3UnderCurrWarn
Bit10= L1OverCurrenWarn
Bit11= L2OverCurrenWarn
Bit12= L3OverCurrenWarn
Bit13= L1LineLossWarn
Bit14= L2LineLossWarn
Bit15= L3LineLossWarn
0
Group
Param
No.
Parameter Name Description Type
Data Size
(bytes)
Scale
Factor
Min Max Default Units