364 Rockwell Automation Publication 193-UM015B-EN-P - November 2013
Appendix B Parameter List
Analog2 Setup
(continued)
496 OutAnMod2Select Assignment of parameter data
value to drive Analog Module 2
Output
USINT 1 1 0= AveragePctFLA
1= ScaledAvgPctFLA
2= PercentTCU
3= GFCurrent
4= CurrentUnbalance
5= AvgLLVoltage
6=VoltLLUnbalance
7= TotalkW
8= TotalkVA
9= TotalkVAR
10= TotalPF
11= UserDLXData
0
497 OutAnMod2FltActn Analog Module 2 Output action
on comms fault
USINT 1 1 0= Zero
1= Maximum
2= Minimum
3= HoldLastState
0
Analog3 Setup
498 OutAnMod2IdlActn Analog Module 2 Output action
on comms idle
USINT 1 1 0= Zero
1= Maximum
2= Minimum
3= HoldLastState
0
499 InAnMod3Ch00Type Assignment for Analog Module 3
Input Channel 00 function
USINT 1 1 0= Disabled
1= 4To20mA
2= 0To20mA
3= 0To10Volts
4= 1To5Volts
5= 0To5Volts
6= 100Pt385
7= 200Pt385
8= 500Pt385
9= 1000Pt385
10=100Pt3916
11= 200Pt3916
12= 500Pt3916
13= 1000Pt3916
14= 10Cu426
15= 120Ni618
16= 120Ni672
17= 604NiFe518
18= 150ohm
19= 1000ohm
20 = 3000ohm
21= 6000ohm
0
500 InAMod3Ch0Format Assignment for Analog Module 3
Input Channel 00 Data Format
USINT 1 1 0= EngUnits
1= EngUnitsTimes10
2= RawProportional
3= ScaledForPID
0
501 InAMod3C0TmpUnit Assignment for Analog Module 3
Input Channel 00 Temperature
Units
USINT 1 1 0=DegreesC
1=DegreesF
0
502 InAMod3C0FiltFrq Assignment for Analog Module 3
Input Channel 00 Filter Freq
USINT 1 1 0=17Hz
1=4Hz
2=62Hz
3=470Hz
0
Group
Param
No.
Parameter Name Description Type
Data Size
(bytes)
Scale
Factor
Min Max Default Units