Rockwell Automation Publication 193-UM015B-EN-P - June 2014 67
System Operation and Configuration Chapter 3
Input Pt05 Assignment (Parameter 201)
Input Pt05 Assignment (Parameter 201) allows the user to assign this digital
input for the following functions:
Table 44 - Input Pt05 Assignment (Parameter 201)
Value Assignment Description
0 Normal Function as a digital input
1 Trip Reset Reset the E300 when it is in a tripped state
2 Remote Trip Force a the E300 to go into a tripped state
3Activate FLA2
Use the value in FLA2 Setting (Parameter 177) for the current based protection
algorithms
4 Force Snapshot Force the E300 to update its Snapshot log
5 Emergency Start Issue an Emergency Start command
6 Test Mode Enable Test Mode monitoring
7 L1 Line Loss Arm Activate L1 Line Loss Protection
8 L2 Line Loss Arm Activate L2 Line Loss Protection
9 L3 Line Loss Arm Activate L3 Line Loss Protection
10 L1 L2 Line Loss Arm Activate L1 and L2 Line Loss Protection
11 L2 L3 Line Loss Arm Activate L2 and L3 Line Loss Protection
12 L1 L3 Line Loss Arm Activate L1 and L3 Line Loss Protection
13 L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection